Question 1

The air intake of the mission-critical server at the top of the rack is measuring 25 C/77 F.

Is this acceptable?


Correct : A

An air intake temperature of 25 C (77 F) at the top of the rack is acceptable according to data center standards and guidelines, such as those from ASHRAE. This temperature falls within the recommended range for inlet temperatures, which is typically between 18C (64F) and 27C (81F).

Detailed Explanation:

ASHRAE standards provide guidelines on acceptable temperature ranges for air intake in data centers to balance cooling efficiency and equipment safety. A temperature of 25C is within the recommended operational range, allowing data centers to optimize energy efficiency while maintaining safe conditions for IT equipment.

EPI Data Center Specialist References:

EPI guidelines align with ASHRAE recommendations for server intake temperatures, confirming that 25C is within acceptable limits for most mission-critical equipment. This ensures the data center maintains an efficient and reliable environment.


Options Selected by Other Users:
Mark Question:

Start a Discussions

Submit Your Answer:
0 / 1500
Question 2

An air-conditioner unit needs to be selected. Two types are available:

Unit-A has a Sensible Heat Ratio (SHR) of 0.7.

Unit-B has a Sensible Heat Ratio (SHR) of 0.9.

From an efficiency point of view, which one should be selected?


Correct : D

From an efficiency standpoint, Unit B with a Sensible Heat Ratio (SHR) of 0.9 is preferable. A higher SHR indicates that a greater proportion of the air conditioner's capacity is dedicated to sensible cooling (temperature reduction) rather than latent cooling (moisture removal). In data centers, sensible cooling is more critical since IT equipment primarily generates heat without adding significant moisture.

Detailed Explanation:

An SHR of 0.9 means that 90% of the cooling capacity is used for sensible cooling, which is more efficient for environments like data centers where humidity control is typically less of a concern. Opting for an air conditioner with a higher SHR ensures that most of the cooling energy is focused on temperature reduction, making Unit B more efficient in this scenario.

EPI Data Center Specialist References:

EPI data center best practices recommend choosing cooling units with higher SHR values in data centers, as they better match the cooling needs of IT equipment. High SHR units improve cooling efficiency by concentrating on sensible heat removal, which is vital for maintaining the optimal thermal environment.


Options Selected by Other Users:
Mark Question:

Start a Discussions

Submit Your Answer:
0 / 1500
Question 3

You are working with a customer who requires a guarantee that THDi levels coming from the UPS should not exceed more than 3% THDi. Furthermore, he wants to run a power-efficient data center. The UPS has a 6-Pulse SCR/Thyristor based rectifier. The current load on the UPS is approximately 80%. The customer indicates they are not expecting any changes on the ICT infrastructure for the next 3 years.

What should you recommend?


Correct : C

Given the customer's requirement to limit Total Harmonic Distortion (THDi) to below 3% and the presence of a 6-pulse SCR/Thyristor-based rectifier, an active harmonic filter is the best solution. A 6-pulse rectifier typically generates higher harmonic distortion, often exceeding 3%, especially under substantial loads like 80%. An active harmonic filter dynamically monitors and compensates for harmonic distortion, effectively reducing THDi and supporting a more power-efficient operation, aligning with the customer's energy efficiency goals.

Detailed Explanation:

Passive harmonic filters can reduce harmonics but are less effective at maintaining low THDi levels under varying loads. Active filters offer real-time correction and can achieve lower THDi levels than passive filters, especially in systems with fluctuating loads or where strict harmonic limits are required. Installing an active harmonic filter will ensure compliance with the specified THDi limits and optimize power quality.

EPI Data Center Specialist References:

EPI guidance on power quality management recommends active harmonic filters for environments where strict THDi levels are necessary. Active filters offer better control over harmonic levels, supporting both compliance and operational efficiency.


Options Selected by Other Users:
Mark Question:

Start a Discussions

Submit Your Answer:
0 / 1500
Question 4

When designing a data center network, your company wants to minimize the number of network switches to manage.

What type of physical cabling layout would be the best choice?


Correct : B

An End of Row (EoR) design minimizes the number of network switches, as multiple racks can share a single switch at the end of a row, reducing switch counts and simplifying management. This design centralizes network switching to fewer points, which reduces the complexity and number of switches required compared to a Top of Rack (ToR) design, where each rack typically has its own switch.

Detailed Explanation:

In EoR designs, each row has a single network switch that handles the connections for all racks within that row. This reduces the number of individual switches needed and centralizes network management, which is ideal for minimizing equipment and simplifying infrastructure in the data center.

EPI Data Center Specialist References:

EPI promotes the EoR design as a way to reduce switch counts and streamline management in data centers. This configuration allows for easier scaling and maintenance while maintaining efficient network connectivity.


Options Selected by Other Users:
Mark Question:

Start a Discussions

Submit Your Answer:
0 / 1500
Question 5

What should you consider when using raised floor tiles with air deflectors or louvers?


Correct : A

Raised floor tiles with air deflectors or louvers are typically heavier than standard tiles due to the additional materials and mechanisms used to direct airflow. The added weight can pose challenges for installation and adjustment, and consideration must be given to the floor's load capacity and ease of maintenance.

Detailed Explanation:

Tiles with deflectors or louvers help direct airflow, enhancing cooling efficiency by focusing cool air where needed. However, these tiles are often heavier, which can affect handling and require reinforced raised floor systems. It's essential to factor in the weight for any floor tile replacements or installations to ensure they are compatible with the raised floor's structural capacity.

EPI Data Center Specialist References:

EPI data center design training mentions the potential impact of heavy tiles on floor handling and load capacity. Data center operators need to plan for safe handling and load-bearing capacity when using such specialized tiles.


Options Selected by Other Users: